Sedimentation Analysis in Seawater Intake Facility

Sediment transport modeling of the PLTU Jawa 9 & 10 seawater intake to predict sediment distribution and the sedimentation rate.

← All case studiesCFD simulation result for Sedimentation Analysis in Seawater Intake Facility

Client

Hutama Karya — PLTU Jawa 9 & 10 2x1000 MW.

Challenge

Suspended sediment entering the seawater intake facility accumulates over time, driving dredging cost and threatening cooling water availability.

Approach

CFD modeling and simulation of seawater with a sediment transport model were performed, using a total suspended solid of 0.123 mg/L, the lowest low water level of -0.913 m, 4 operating ACWP at 5,430 m3/hour each and 5 operating CWP at 101,600 m3/hour each.

Result

Sand volume fraction contours showed the sediment distribution inside the facility and where deposits concentrate along the basin floor.

Client outcome

The sedimentation rate inside the seawater intake facility was calculated, allowing dredging planning and intake operation to be based on quantified figures.